執(zhí)行器EG-6P-10P
EG-6P/PC, EG-10P/PC Actuator Manual 82566
The EG-10P actuator is suitable for use in Class I, Division 1, Groups B, C, and
D per UL for the US or non-hazardous locations only.
The EG-10P actuator is suitable for use in Class I, Division 2, Groups B, C, and
D per UL for the US or non-hazardous locations only.
The EG-10P actuator is suitable for use in Class I, Division 2, Groups B, C, and
D per CSA for Canada and UL for the US or non-hazardous locations only.
The EG-10P is suitable for use in European Zone 2, Groups A, B, C, and D
environments.
The EG-10P is suitable for use in European Zone 1, Groups A, B, C, and D
environments per LCIE.
Wiring must be in accordance with North American Class I, Division 1 or 2 or
European Zone 1 or 2 wiring methods as applicable, and in accordance with the
authority having jurisdiction.
Field Wiring must be suitable for at least 90 °C.
Connect ground terminal to earth ground.
Each EG-10P Zone 1 actuator must be provided with a 900 mA maximum fuse to
be installed before the actuator.